Configuration Menu: Click to be brought to the configuration menu of the Model 100.

Help: Click to go to the main Model 100 Help menu (opens in a separate window).

Access

Status: Select Disabled or Enabled. Factory default is Enabled. When enabled the remote user can access SNMP objects with correct community names. Model 100 can still generate traps if access status is disabled.
Note: In order to function, port 161 must be open through any firewalls between the PC and the Model 100.

Read Community Name: Enter a read community name, up to 31 characters. Factory default is public.

Read-Write Community Name: Enter a read-write community name, up to 31 characters. Factory default is private.

Submit: Click Submit to send the Access changes to the system.

Trap (Notification)

Status: Select Disabled or Enabled. Factory default is Disabled.

Minimum Trap Interval: Select 1 min, 10 min, 30 min, 1 hr, 2 hr, 4 hr, 8 hr. Factory default is 1 min.

Trap Community Name: Enter a trap community name, up to 31 characters. Factory default is public.

Receiver Address: Enter the receiver address, up to 31 characters. Factory default is blank.

Version: Select v1 or v2c. Factory default is v2c.

Submit: Click Submit to send the Trap (Notification) changes to the system.

Trap Trigger

Threshold (dB): Enter a number in dB between 0 and 160 for the threshold. Factory default is 94.

Measurement Type: Select SPL Fast, SPL Slow, Leq 1 sec, Leq 10 sec, Leq 1 min, Leq 5 min, Leq 10 min, Leq 15 min, Leq 30 min, Leq 1 hr, Leq 8 hr, Leq 24 hr, Leq Continuous, User Ln, L1, L10, L50, L90, or Peak C. Factory default is SPL Fast.

Submit: Click Submit to send the Trap Trigger changes to the system.

Test Trap: Click Send to send a test trap. Note: Trap status must be enabled to send a test trap.

Error Status: Shows --- or current error. See Configuration Menu Help for a description of all error messages.

Clear Error Message: Click to clear error message.